Exhaust Gas Analysis - Flue Gas Analysis - Leak Detectors - Refrigerant Monitors
The MVR-300™ detector is specifically designed to provide continuous monitoring for refrigerants associated with high-efficiency, high volume refrigerant cooling and heating systems, such as VRF/VRV (Variable Refrigerant Flow/Variable Refrigerant Volume) sytems. Typical applications include hotels, dormitories, hospitals, office buildings, and apartment buildings.
The MVR-300™ audible and visual alarms alert occupants and simultaneously communicate to Building Management Systems/Building Automation Systems (BMS/BAS). Two on-board relays can be used to close valves, activate alarm devices and exhaust fans or initiate emergency calls to rescue teams.
The on-board Modbus RTU interface provides real-time information about concentrations, status and settings. It also enables custom configuration of the MVR-300™ to any application specific requirements using multiple Modbus registers.
The MVR-300™ is designed for easy installation and simple maintenance.
The new MVR-300™ supersedes the IAM-100 / IAM-C product range.
Ideal for applications like:
Hotels
Office Buildings
Appartements
Schools
Hospitals
FEATURES & BENEFITS:
Detects R-410a, R-407c, R-404a, R32 (Other refrigerants on request)
Fast-responding, refrigerant-specific sensor
Two relays and Modbus Communications for notifying building management & initiate counter measures
Easy to use
Easy to install - Fits in standard electrical boxes for easy installation
Easy to service - Self diagnostics and simple field calibration for easy maintenance
Unique plug-in field replaceable pre-calibrated sensor for low cost of ownership
Low profile / flush mount for aesthetically non-intrusive appearance
Alarm options (LED, buzzer, two levels, configurable delay and fail-safe) to alert occupants and remotely inform building management of alarm location for rapid response as required
Gas | R410A |
Following is a list of refrigerants that can be detected:
Specific Transmitters: R32, R404a, R407c, R410a Please contact us for refrigerants not listed. |
Technical Data:
Sensor: | 5-8 year life |
Range: | 0 - 10000 ppm |
Alarm - low: | 2000 ppm |
Alarm - high: | 4000 ppm |
Power Supply: | 100 -240VAC, 50/60 Hz, 4W max. |
Indicator: | Tricolor LED (red, amber, green) |
Audible Alarm: | Buzzer (80db) |
Relay: | 2 relays SPDT; Configurable, 1A @ 30VDC; 1A @ 125 and 230VAC |
Communication: |
Modbus RTU
|
Alarm Delay: | Selectable; 0 to 15 minutes |
TemperatureRange: | 0°C to +50°C |
Storage Conditions: | -20°C to +40°C |
Humidity Range: | 5-90 % rh, non condensing; 0 - 2000m Höhe |
Approvals: | CE, UL/CSA/IEC/EN 61010-1 |
Dimensions&Weight: | 150 x 105 x 45 mm; 230g |
IM Env. Equip. Germany GmbH reserves the right to adopt technical modifications without prior notice.
Copyright © 2019 IM GmbH