CFC: |
R11, R12, R113, R114, R502, HFP |
HFC: |
R125, R-134a, R236FA, R245Fa, R32, R-404a (HP62), R-407a, R-407c (AC9000), R-407F, R-410a (AZ20), R422a, R422d, R427a, R-507 (AZ50), R-508b (SUVA95) |
HCFC: |
R21, R22, R23, R123, R124, R227, R500, R503, R401A (MP39),
R402A (HP80), R402 (HP81), R408A, R409A, R236FA, R125, R245FA, R422A, R422D, R427A |
Halon: |
H1211, H1301, H2402 |
Other: |
FA188, FC72, H1234YF, H1234ZE, N1230, N7100, N7200, N7300, N7600, R424A, R426A, R438A, CUSTOM |
Sensor: |
NDIR, 7 - 10 years |
Measurement_Range:__ |
All gases 0 to 10,000 ppm |
Accuracy: |
Most gasses: ±1 ppm ±10% of reading from 0-1000 ppm (R11, R22, and R113 ±10 ppm ±15% of reading 0-1000 ppm) |
Coverage: |
4 point standard, expandable to 16 points in 4 point increments |
Front Panel: |
3 Indicator lights:
• Green Monitor is powered on. LED glows during normal operation; flashes when unit is in warm-up mode
• Red Alarm. LED flashes when any point has exceeded the alarm setting.
• Yellow Fault. LED flashes when there is a system fault |
Sampling Mode: |
Automatic or manual (hold) |
Re-Zero: |
Auto or on zone change |
Response Time: |
5 to 315 seconds – depending on air line length and number of zones |
Monitoring Distance: |
1,200 ft (366 m) maximum for combined length of sample + exhaust tubing (each zone) |
Conditioned Signal: |
Dual optional 4-20 mA DC isolated outputs. Channel 1 = zone area, Channel 2 = PPM |
Alarms: |
Four SPDT alarm contacts rated 2A at 250 VAC (inductive) 5 A at 250 VAC (resistive). Three are assigned to PPM level alarms, one assigned to system faults. |
Communications: |
Full two-way communications with Remote Display Module or Building Management System via RS-485 serial interface. RS-232C communications port standard. |
Operating Temp.: |
0 to 50°C |
Ambient Humidity: |
5 to 90%, non condensing |
Power Supply: |
100 to 240 VAC, 50/60 Hz, 20 W |
Dimensions |
31.06 cm x 34.80 cm x 12.60 cm |
Weight |
6.8 kg |